Flow Phenomena
Cavitation Index (σ, Kc, xFz)
Several dimensionless numbers predict where a valve sits on the cavitation scale; the three most met in practice:
- Sigma (σ) = (P2 − Pv) / (P1 − P2). Higher σ means more margin. Each valve/trim has characteristic threshold values (incipient, constant, incipient damage, choking) determined by test; comparing installed σ with the trim's σ values tells you which regime you are in.
- Kc (ISA-75.02 style) is the ratio at the incipient-damage condition — the value of (P2−Pv)/(P1−P2) below which material loss begins.
- xFz (IEC 60534-8-x style) is the pressure-drop ratio of the choked condition, used with the full standard's cavitation and noise procedures.
All three encode the same physics: the margin between the downstream pressure and the vapour pressure, scaled by the pressure drop. The practical use is the same — compute your σ, fetch the trim's certified thresholds, and keep the operating point in the non-damaging region, or select multi-stage trim that raises the thresholds. Our liquid Cv calculator flags the choked-flow condition as a first screen.
Related glossary terms
More like this: browse the full control valve glossary, or see how the terms fit together in How a Control Valve Works.
Editorial note. Definitions reflect common industry usage and the conventions of IEC 60534 and ISA-75. Engineering content is educational; always verify against the applicable standard and manufacturer data.